Ir arriba
Información del artículo

Modeling of thermal generating units for automatic generation control purposes

I. Egido, F. Fernández-Bernal, L. Rouco, E. Porras, A. Saiz-Chicharro

IEEE Transactions on Control Systems Technology Vol. 12, nº. 1, pp. 205 - 210

Resumen:
A simple discrete time model of a thermal unit has been formally developed for designing automatic generation control(AGC) controllers. This model has been developed using data obtained from specific tests and historical records. This model consists of a nonlinear block followed by a linear one. The nonlinear block consists of a dead band and a load change rate limiter, while the linear block consists of a second-order linear model and an offset. Although most of these elements have already been included in unit models for AGC presented in the literature, a certain mix up exists about which of them are necessary. This is clarified in this paper. It has been found that the unit response is mainly determined by the rate limiter, while the other model components are used for a better fitting to the real response. An identification procedure is proposed to estimate the values of the model’s parameters.


Palabras Clave: Automatic generation control (AGC), dead band, identification procedure, load change rate limiter, thermal unit model


Índice de impacto JCR y cuartil WoS: 0,923 (2004); 4,900 - Q1 (2023)

Referencia DOI: DOI icon https://doi.org/10.1109/TCST.2003.821959

Publicado en papel: Enero 2004.



Cita:
I. Egido, F. Fernández-Bernal, L. Rouco, E. Porras, A. Saiz-Chicharro, Modeling of thermal generating units for automatic generation control purposes. IEEE Transactions on Control Systems Technology. Vol. 12, nº. 1, pp. 205 - 210, Enero 2004.


pdf Previsualizar
pdf Solicitar el artículo completo a los autores